[18] The 4-way valve of 3-pipe valve box reversing failure
 
 
If the 4-way valve of 3-pipe 
valve box is internal leakage
Yes
No
No
No
Yes
Yes
Yes
No
No
Yes
Check if the TC1 and TC2 of indoor 
unit are normal, if the resistance is 
right? If the connect well?       
If the 4-way valve of outdoor 
unit is internal leakage
Replace the driver module, if it is normal
If exceeds the running range of the 
outdoor unit
Adjust  it  correctly  by  after-sales 
personnel on site.
Replace the driver module
If the pressure difference between 
high and low pressure less than 
0.4Mpa before the failure occurs, 
replace the inverter compressor
Adjusting the running range
Adjust it  correctly by after-sales 
personnel on site.
Adjust it  correctly by after-sales 
personnel on site.
Note: abnomity conrmation conditions
For MRVIII-RC system,  the  outdoor  unit  is running normally,  when  the  4-way valve of valve box is 
power on and its connected heating indoor unit's parameter satisfy following conditions
• &              •  When 4-way valve of valve box is ON
 
                   • TC2 ≤ CT-20
o
C lasts for 5min
                   • or              • TC1 ≤ 0
o
C lasts for 5min
                                       • TC1 ≤ master unit Ps_temp+10
o
C lasts for 5min