The wiring for the power line  of  indoor  unit, the wiring between indoor and outdoor  units  as  well as the wiring 
between indoor units:
 ■ The electrical power line and signal lines must be fastened tightly.
 ■ Every indoor unit must have the ground connection.
 ■ The power line should be enlarged if it exceeds the permissible length.
 ■ Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of 
signal lines of outdoor units grounded at one point. 
 ■ It is not permissible if the whole length of signal line exceeds 1000m.
                    Items
Total   
current of  
indoor units
 
(A)
Cross 
section 
(mm
2
)
Length 
(m)
Rated  
current of  
overow  
breaker
 
(A)
Rated current of residual 
circuit breaker (A) 
ground fault Interruptor (mA)  
response time (S)
Cross sectional  
area of signal Line
Outdoor-indoor 
(mm
2
)
Indoor-indoor 
(mm
2
)
 <10   2 20 20 20 A,30 mA,0.1S or below  
2 cores×(0.75-2.0)mm
2
 
shielded line
≥10 and <15 3.5 25 30 30 A,30 mA,0.1S or below
≥15 and <22  5.5 30 40 40 A,30 mA,0.1S or below
≥22 and <27    10 40 50 50 A,30 mA,0.1S or below
Signal wiring of wired controller
Length of signal line (m) Wiring dimensions
≤ 250 0.75mm
2
×3 core shielded line
※
 
The shielding lay of the signal line must be grounded at one end.
※
 
The total length of the signal line shall not be more than 250m.