Video Security Control Panel User Manual
{1} The programming command address of control panel tamper-proof disconnecting linkage siren is:
511;
{2} It indicates whether to link the siren or not;
{3} End the command.
Testing Report Settings 3.1.25
The testing report is used to validate the communication of control panel and alarm center. The detailed
operation is show as follows.
{1} Testing Report Programming Address: 513
{2} Enable/Disable the testing report
{3} Timer of the testing report. It indicates the time of firstly sending the test report. The initial value is
the time of enabling the test report.