3 Product Description  F3 AIO 8/4 01 
Page 14 of 54  HI 800 161 E Rev. 1.01 
Measured values for voltage on AI with line monitoring of DO 
Voltage drop 
R
series resistor
 
Voltage drop 
R
solenoid valve
 
Voltage drop 
R
Shunt
 
Values for AI 
(with FSx000 resolution) 
    FS1000 FS2000 
Output DO False or 0 
(output DO is deactivated; de-energized state) 
25.08 V  1.15 V  0.15 V  14  28 
Output DO True or 1 
(output DO activated) 
-  21 V  3 V  300  600 
Break in the field wiring 
- - 0 V 0 0 
Short-circuit in the field wiring or actuator 
-  0 V  26.8 V  1000
1)
 2000
1)
 
1)
  maximum resolution of the analog inputs AI with voltage limited to 12 V by Z-diode 
Table 7:  Voltage Values with Line Monitoring of DO 
 
 
Illustration of Figure 1 and Table 7 
 
1. Open-circuit: 
The supply voltage of the series resistor (transmitter voltage) fluctuates within a tolerance 
range, see Specifications in 
Table 18. For this reason, the voltage drops on the resistors 
can change slightly. Within the fluctuation range, a measurable voltage drop is definitely still 
detected on shunt R
shunt
. 
The series resistor was dimensioned such that when DO = FALSE, the voltage drop on the 
solenoid valve is as low as possible (valve is slightly warmed up) and the voltage drop on 
the shunt is still measurable. 
The shunt R
shunt 
was measured with dependence on the solenoid valve resistance such that 
if the output DO is activated (DO = TRUE), the voltage drop on the solenoid valve is higher 
than the switching threshold of the solenoid valve, i.e., the coil of the solenoid valve is 
energized. 
Additionally, the shunt R
Shunt
 is designed such that with any switching state of the output 
DO (TRUE or FALSE), a measurable voltage drop results (values for AI > 10, see 
Table 7). 
On the other hand, if field wiring breakage occurs within the red-colored area, voltage drops 
are no longer present on the shunt. 
An open-circuit within the red-colored area (see 
Figure 1) can be monitored through the 
voltage drop on the shunt R
shunt
 , i.e., the input value of AI, see Table 7. 
To allow line monitoring, the value of AI must be evaluated in the logic of the user program. 
i 
Connect the series resistor R
series resistor 
and the shunt R
shunt
 directly to the terminals of the 
controller or remote I/O to maximize the monitored line area.