F3 AIO 8/4 01  4 Start-Up 
HI 800 161 E Rev. 1.01  Page 41 of 54 
4.5 Connection Variants 
This chapter describes the correct wiring of the remote I/O in safety-related applications. 
4.5.1 Connecting Proximity Switches 
Proximity switches can be evaluated with the analog inputs using the wiring shown in 
Figure 10. 
The proximity switch is connected to its supply via the line resistor RL. Afterwards, it is 
connected in series to the R1 resistor. 
 
 Proximity Switch 
  Line Resistance of < 50  
  Z 7309 Shunt Adapter 
  R1 = 500  
  F3 AIO 8/4 01 Remote I/O 
 Supply 
 Analog Input 
 Ground 
Figure 10:  Proximity Switch on Analog Inputs 
 
i 
Unshielded cables may be used (zone A, in accordance with EN 61131 – 2: 2007). 
Shielded cables must be used if the system is located in a hostile EMC environment (zone 
B or C). The shielding must be earthed by attaching it to the shroud.