4 Start-Up F3 AIO 8/4 01
Page 36 of 54 HI 800 161 E Rev. 1.01
4.3.3 Analog Outputs F3 AIO 8/4 01
The following tables present the statuses and parameters for the output module (AO 4) in
the same order as given in the Hardware Editor.
4.3.3.1 Module Tab
The Module tab contains the following system parameters.
System parameter
Data
type
R/W Description
AO.Error Code WORD R Error codes for all analog outputs
Coding Description
0x0001 Module fault.
0x0002 MOT test: Safety switch 1 faulty
0x0004 MOT test: Safety switch 2 faulty
0x0008 FTT test of test pattern faulty
0x0010 FTT test: Error while checking coefficients
0x0400
FTT test: 1st temperature threshold
exceeded
0x0800
FTT test: 2nd temperature threshold
exceeded
0x2000 MOT test: status of safety switches
0x4000
MOT test: active shutdown via watchdog
faulty
Module.Error Code WORD R Module error code
Coding Description
0x0000
I/O processing, if required with errors, see
other error codes
0x0001 No I/O processing (CPU not in RUN)
0x0002 No I/O processing during the booting test
0x0004 Manufacturer interface operating
0x0010 No I/O processing: incorrect configuration
0x0020 No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module.SRS UDINT R Slot number (System Rack Slot)
Module.Type UINT R Type of module, target value: 0x0069 [105
dec
]
Table 28: SILworX - System Parameters for the Analog Outputs, Module Tab