EtherNet/IP
262
10.2
EtherNet/IP Parameters
UM Basic Configuration L3P
Release
7.1
12/2011
Switch
Temperature
ID 02 Struct{INT RO Temperature °F, INT RO Temperature °C}
Reserved ID 03 Always 0, attribute is reserved for future use.
Switch Max
Ports
ID 04 UINT (16 bit) RO Maximum number of Ethernet Switch Ports
Multicast
Settings (IGMP
Snooping)
ID 05 WORD (16 bit) RW
Bit 0 RW IGMP Snooping (1: enabled, 0: disabled)
Bit 1 RW IGMP Querier (1: enabled, 0: disabled)
Bit 2 RO IGMP Querier Mode (1: Querier, 0: Non-Querier)
Bit 4-6 RW IGMP Querier Packet Version 1: V1, 2: V2, 3: V3, 0: Off (IGMP
Querier disabled)
Bit 8-10 RW Treatment of Unknown Multicasts (Railswitch only): 0: Send To
All Ports, 1: Send To Query Ports, 2: Discard
Switch Existing
Ports
ID 06 ARRAY OF DWORD
a
RO Bitmask of existing Switch Ports
Per Bit starting
with Bit 0
(means Port 1)
1: Port existing, 0: Port not available. Array (bit mask) size is
adjusted to the size of maximum number of Switch ports (e.g.
a max. no of 28 ports means that 1 DWORD is used (32 bit)).
Switch Port
Control
ID 07 ARRAY OF DWORD
a
RW Bitmask Link Admin Status Switch
Ports
Per Bit starting
with Bit 0
(means Port 1)
0: Port enabled, 1: Port disabled. Array (bit mask) size is
adjusted to the size of maximum number of Switch ports
(e.g. a max. no of 28 ports means that 1 DWORD is used (32
bit)).
Switch Ports
Mapping
ID 08 ARRAY OF USINT (BYTE, 8 bit) RO Instance number of the
Ethernet Link Object
Starting with
Index 0
(means Port 1)
All Ethernet Link Object Instances for the existing Ethernet
Switch Ports (1..N (maximum number of ports)). When the
entry is 0, the Ethernet Link Object for this port does not exist.
Switch Action
Status
ID 09 DWORD (32 bit) RO
Bit 0 Flash write in progress
Bit 1 Unable to write to flash or write incomplete
a. RS20/RS30/RS40, MS20/MS30, OCTOPUS, PowerMICE, RSR20/RSR30, MACH 100 and
MACH 1000: 32 bit;
MACH 4000: 64 bit
Attribute ID/Bit No. Description
Table 36: Hirschmann Ethernet switch Agent Object