Fire Alarm Control Panel Compact
32 FB 798238.GB0 / 10.14
6 Settings
3
1 display functions
2 system timings
3 control timings
4 language
settings
3
5
JKL
Fig. 44: >Settings< menu screen
6.1 Display functions
1
3
1 descript. : [panel 1 ]
2 code installer : 123
3 code operation : 0123
code cust. data : 0815
- country spec. : germany
- fault evaluation MZD/MDD : on
- disable MZD/MDD
display functions 1/3
3
- reset fauls if panel reset : off
- indicate pre-alarm detector : on
- disable HMI monitoring : off
- diagnostic notice detector : on
- buzzer technical alarm : off
- buzzer cover contact : off
- buzzer pre-alarm : off
display functions 2/3
1 buzzer verification time : off
2 acoustic mute : on
display functions 3/3
3
Fig. 45: >Settings< menu screens
Acoustic mute available
2ABC
Switching this function On or Off programs the “acoustic
alarm device” (buzzer) key to have either a mute or alarm
device switch-off effect.
Switch-off /mute acoustic alarm devices
The buzzer switch-off or muting is shown in each case with
the yellow LED on the control panel.
Switch-off acoustic alarm devices are switched off
and will not be activated by an alarm
event.
Mute: The triggered acoustic alarm devices
were reset and muted. They will be
triggered with each new alarm signal.
Observe standards and requirements!
Observe the information on the configuration and commissioning of the FACP in accordance with
national standards/directives and local requirements.