MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018 81
Master Programming Level Programming
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed:
Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour Test to the Central Station. A flashing
cursor will appear in the lower left corner of the screen. Enter a four digit number representing the test time using military time (0000 =
midnight and 2359 = 11:59PM).
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR T TIME
Primary/Secondary Screen #1
24 HOUR TEST TIME
ENTR USING 24HR TIME
RANGE 0000-2359
24 Hour Test Time Screen