Fire Alarm Control Panel LT-32 / LT-159
M-168.1-SERIE-LT-EN / 08.2022 11
4 SPECIFICATIONS
• 4,3'' / 109,2 cm Touch-screen graphical color display, 480 x 272 pixel with back illumination and backlit membrane buttons
• LT-32 manage up to 32 wireless or addressable devices
• LT-159 manage up to 159 addressable devices, mainly wireless
• 16 Zones
• Fire and Fault relay NO/NC configurable using related jumpers
• Two sounder circuits in the LT-32 and one sounder circuit in LT-159 (max. load 50 mA each)
• Output delays max. 10 minutes (according to EN 54)
• 8 illuminated status icons: Fire, System Fault, General Fault, Disable, Test, Sounder Fault, Power Fault, Power
• 4 operating buttons: Reset Panel, Silence Buzzer, Silence Sounders, Evacuate
• The internal panel buzzer, provides an audible alert to the authorized user, to take immediate action whenever the system detects any condition such as a fire or
fault event. Depending on the type of event, the buzzer activates (sounds) using a different tone pattern. The SILENCE BUZZER control button is used to silence
(mute) the internal buzzer after it has switched on following an event. This control is available at all access levels, without a need for PIN code
• AC power supply with different plug options with a maximum rate power of 24 W
• Autonomy in standby and alarm time, in absence of main power, are based on the system configuration. Please refer to Honeywell Loop Calculator for more details
• Panel Is specified for small applications, especially for wireless devices. Max. loop distance: 500 m, cable resistance below 10 Ohm (depending on the loop load
current)
• 6 AA-size 2,700 mAh Nickel metal hydride (Ni-MH) battery
• Log and configuration through USB port type B, available in future releases
• Imin= 200 mA
• Imaxa= 500 mA
• Imaxb=1,5 A
• Maximum RiMin = 0,7 Ohm
• Certified EN 54-2 / AC / A1
• Certified EN 54-4 / A1 / A2
• Certified LVD 62.368-1:2014+A11