EasyManuals Logo

Honeywell LT-32 User Manual

Honeywell LT-32
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Fire Alarm Control Panel LT-32 / LT-159
M-168.1-SERIE-LT-EN / 08.2022 13
4.2 Electrical specifications
External power supply: 100 ... 240 Vac, 50 ... 60 Hz
Power connection terminal: European standard AC. UK connector optional
Maximum power consumption: 24 W
Supervised sounder outputs (1 in the LT-159, 2 in the LT-32), each with max. 50 mA
Max. 500 m distance depending on the cable section and current consumption in alarm
1 Alarm relay with configurable NC/NO contact
1 Fault relay with configurable NC/NO contact
4.3 Environmental specifications
Climate classification: K5 (IEC 721-2-3)
Temperature range: -5ºC ... 40ºC
Relative humidity: 5% ... 95% non-condensing
Control panel protection rating: IP 30 (acc. EN 60529)