EasyManua.ls Logo

Honeywell MA Series - Disabling Detector Status; Procedure for Disabling Detectors; Disabling Module Status; Procedure for Disabling Modules

Honeywell MA Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAx panel Fire Detection System
24 M-167.3-Serie-MA-EN / 11.2021
Modify status - detectors
The display shows the first device of the first line by default. To select another device, use the function buttons.
When a detector is
disabled
, the control unit is prevented from
receiving alarms and fault signalling from the sensor.
To
disable
a detector, select it using the function buttons. Once
the device has been selected, press the enter button
, us
e the
arrow buttons
 to select YES
and then press the enter button
to confirm the disablement.
Modify status - modules
The display shows the first device of the first line by default. To select another device, use the function buttons.
When a module is
disabled
, the control unit is prevented from
receiving alarms and fault signalling from the module.
To
disable
a module, select it using the function buttons. Once
the device has been selected, press the enter
button
, use the
arrow but
tons to select YES and then press the enter
button
to confirm the disablement.
Modify status zones
The display shows the first zone by default. To select another zone, use the function buttons.
When a zone is
disabled
, the control unit is prevented from
receiving alarms and fault signalling from all the points which
belong to the zone.
To disable a zone, select it using the function buttons. Once the
zone has been selected press the enter button , use the arrow
buttons
 to select “YES” and then press the enter button
to confirm the disablement.

Related product manuals