50 MODBUS-GW Installation and Operation Manual — P/N LS10015-000NF-E:C2 4/30/2019
System Troubles
35011
0 ANNUN.57 TROUBLE 8 ANNUN.61 TROUBLE
1 ANNUN.57 NO ANSWER 9 ANNUN.61 NO ANSWER
2 ANNUN.58 TROUBLE 10 ANNUN.62 TROUBLE
3 ANNUN.58 NO ANSWER 11 ANNUN.62 NO ANSWER
4 ANNUN.59 TROUBLE 12 ANNUN.63 TROUBLE
5 ANNUN.59 NO ANSWER 13 ANNUN.63 NO ANSWER
6 ANNUN.60 TROUBLE 14 ANNUN.64 TROUBLE
7 ANNUN.60 NO ANSWER 15 ANNUN.64 NO ANSWER
35012
0 GROUND FAULT LOOP 3 8 STYLE 6 NEG. LOOP 3
1 GROUND FAULT LOOP 4 9 STYLE 6 NEG. LOOP 4
2 GROUND FAULT LOOP 5 10 STYLE 6 NEG. LOOP 5
3 GROUND FAULT LOOP 6 11 STYLE 6 NEG. LOOP 6
4 GROUND FAULT LOOP 7 12 STYLE 6 NEG. LOOP 7
5 GROUND FAULT LOOP 8 13 STYLE 6 NEG. LOOP 8
6 GROUND FAULT LOOP 9 14 STYLE 6 NEG. LOOP 9
7 GROUND FAULT LOOP 10 15 STYLE 6 NEG. LOOP 10
35013
0 STYLE 6 POS. LOOP 3 8 PRINTER SUPERVISORY
1 STYLE 6 POS. LOOP 4 9 BUZZER SUPERVISORY
2 STYLE 6 POS. LOOP 5 10 CRT SUPERVISORY
3 STYLE 6 POS. LOOP 6 11 PRINT QUEUE FULL
4 STYLE 6 POS. LOOP 7 12 MEMORY LOSS
5 STYLE 6 POS. LOOP 8 13 PRINTER COVER OPEN
6 STYLE 6 POS. LOOP 9 14 PRINTER PAPER OUT
7 STYLE 6 POS. LOOP 10 15 PRINTER OFF LINE
35014
0 Workstation Fan Failure 8 STYLE 4 SHORT A LOOP 3
1 UPS Failure 9 STYLE 4 SHORT B LOOP 3
2 MANUAL MODE ENTERED 10 STYLE 4 SHORT A LOOP 4
3 NCM COMM LOSS 11 STYLE 4 SHORT B LOOP 4
4 STYLE 4 SHORT A LOOP 1 12 STYLE 4 SHORT A LOOP 5
5 STYLE 4 SHORT B LOOP 1 13 STYLE 4 SHORT B LOOP 5
6 STYLE 4 SHORT A LOOP 2 14 STYLE 4 SHORT A LOOP 6
7 STYLE 4 SHORT B LOOP 2 15 STYLE 4 SHORT B LOOP 6
35015
0 STYLE 4 SHORT A LOOP 7 8 GENERAL PS FAULT
1 STYLE 4 SHORT B LOOP 7 9 STYLE 6 SHORT LOOP 1
2 STYLE 4 SHORT A LOOP 8 10 STYLE 6 SHORT LOOP 2
3 STYLE 4 SHORT B LOOP 8 11 STYLE 6 SHORT LOOP 3
4 STYLE 4 SHORT A LOOP 9 12 STYLE 6 SHORT LOOP 4
5 STYLE 4 SHORT B LOOP 9 13 STYLE 6 SHORT LOOP 5
6 STYLE 4 SHORT A LOOP 10 14 STYLE 6 SHORT LOOP 6
7 STYLE 4 SHORT B LOOP 10 15 STYLE 6 SHORT LOOP 7
Table E.1 System Troubles Register Map (Continued)
Register Bit No. System Trouble Name Bit No. System Trouble Name