NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14 119
Appendix H: Intelligent Sounder Base Programming
and Operation
The NFS2-640 is compatible with the B200 Intelligent Sounder Base. This sounder base allows for
multiple tone generation that is user programmable via VeriFire Tools.
Programming the Intelligent Sounder Base into the Control Panel:
Once the sounder base has been installed and a detector has been plugged into the sounder base,
you can do one of the following to program the sounder base into the control panel:
Autoprogram—Perform an autoprogram at the control panel. The sounder base will have the
same SLC device address as the detector installed on the sounder base. Once the Autoprogram
is performed, the display will show the number of sounder bases installed on the control panel.
Refer to Section 2.3.2, “Autoprogram the Control Panel (1=auto)”, on page 15.
VeriFire Tools —Using VeriFire™ Tools, program the detector that is to be installed in the
sounder base and select the Intelligent Sounder Base option. Refer to the VeriFire Tools Help
File for additional information.
Intelligent Sounder Base Options:
The sounder base has user programmable options that can be modified via VeriFire Tools. These
features and their defaults are as follows:
Table H.1 Intelligent Sounder Base Options
Feature: Description and Options: Default:
Zone Mapping The sounder base allows for up to three (3)
zones to be programmed for specific tone
generation. The tones available are:
Continuous
Temp-3
Temp-4
•March Time
The first of the three zones has the highest
priority, the second zone has second priority,
and the third has third priority.
No zones mapped.
(When set as default, a fire alarm
will generate a Temp-3 tone and a
CO alarm will generate a Temp-4
tone.)
Silence and
Resound
The intelligent sounder base may be
programmed for silenceable operation as well
as signal resound. The silence and resound
options available are:
No silence
Silence and resound by Fire Alarm
Silence and resound by Supervisory
Silence and resound by CO alarm
Silence and no resound
Silenceable and Resound by Fire

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-640/E and is the answer not in the manual?

Honeywell Notifier NFS2-640/E Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-640/E
CategoryControl Panel
LanguageEnglish

Related product manuals