Transmitter Mounting
Transmitter location
Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide 17
February 2013
2.4 Transmitter location
Pressure models
Table 2-5 Pressure models
Process Suggested location Explanation
Gases Above the gas line
The condensate drains away from the
transmitter.
Liquids
• Below but close to the
elevation of the process
connection.
• Level with or above the
process connection.
• This minimizes the static head
effect of the condensate.
• This requires a siphon to protect
the transmitter from process
steam. The siphon retains water as
a “fill fluid.”
2.5 Conduit / Cable Entries
NOTICE
THIS PRODUCT IS SUPPLIED WITH PLASTIC DUST PLUGS IN THE
CONDUIT/CABLE GLAND ENTRIES. IT IS THE USERS RESPONSIBILITY TO
PROVIDE CABLE GLANDS, ADAPTORS AND/OR BLANKING PLUGS SUITABLE
FOR THE ENVIRONMENT IN WHICH THIS PRODUCT IS INSTALLED. WHEN
INSTALLED IN A HAZARDOUS LOCATION THE CABLE GLANDS, ADAPTORS
AND/OR BLANKING PLUGS SHALL ADDITIONALLY BE SUITABLE FOR THE
HAZARDOUS LOCATION, THE PRODUCT CERTIFICATION AND ACCEPTABLE TO
THE AUTHORITY HAVING JURISDICTION FOR THE INSTALLATION
Summary
Table 2-6 Conduit entry plugs and cable glands for your XYR 6000 transmitter.
Factory Part
No.
Description
Environmental
rating
Ambient Hazardous Location Certification
50000547-001 M20 Conduit Plug IP66-68, 4X, 6P
–40 – 85ºC
–40 – 185ºF
ATEX
EEx de IIC
50021832-002 ½ NPT Conduit Plug
IP66-68, 4/4X,
6/6P
–40 – 85ºC
–40 – 185ºF
ATEX
EEx d IIC;
CSAcus CL I, Zone 1, Ex/AEx d IIC;
CL I, Div 1 & 2, GP ABCD; CL II, Div
1 & 2, GP EFG; CL III, Div 1 & 2
50023232-001 M20 Cable Gland IP68
–40 – 100ºC
–40 – 212ºF
-----------------------------------
50023212-001 ½ NPT Cable Gland IP68
–40 – 100ºC
–40 – 212ºF
-----------------------------------