3. Process Insertion
HLAI models
28 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12
February 2013
3.2 HLAI models
Connect wiring
Step Action
1
See Figure 3-5. Open the rear end cap (opposite end from display) by loosening the M3 locking
screw and unscrewing the end cap.
2
Open the cable gland (on right side below antenna). (Cable gland must be ordered as an option.)
3
Feed wiring (allowed diameter 6 to 8 mm) from other transmitter through the cable gland and
connect to terminal block using either voltage or current but not both. See Figure 3-6 or Figure
3-7. For hazardous locations see info starting on page 55.
4
Plug battery connector into batteries.
5
Close rear end cap and cable gland.
6
Tighten M3 locking screw on the rear end cap.
Figure 3-5 HLAI connection
1
2
3
5
4
6
+
-
0-5V
1-5V
+
-
1
2
3
5
4
6
+
-
0-5V
1-5V
+
-
Figure 3-6 Voltage input wiring
1
2
3
5
4
6
+
-
0-20 mA
4-20mA
+
-
1
2
3
5
4
6
+
-
0-20 mA
4-20mA
1
2
3
5
4
6
+
-
0-20 mA
4-20mA
+
-
Figure 3-7 Current input wiring
To voltage/current
source. See Figure
3-6 and Figure 3-7.