2. Transmitter Mounting
Remote Seal Transmitter Mounting
20 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12
February 2013
2.7 Remote Seal Transmitter Mounting
XYR 6000 transmitters furnished with remote diaphragm seals (Model STRWxxx) can be mounted using
the optional mounting brackets. Follow the guidelines below to determine the mounting position of the
transmitter for the given secondary capillary fill fluid.
Table 2-8 Remote Seal Transmitter Mounting
IF the Capillary (Secondary) Fill is: THEN mount the Pressure Transmitter:
Silicone DC® 200
no greater than 22 feet (6.7 meters) above the lower
remote seal.
Silicone DC® 704
no greater than 19 feet (5.8 meters) above the lower
remote seal.
Chlorotrifluorethylene (CTFE)
no greater than 11 feet (3.4 meters) above the lower
remote seal.
Note: The combination of tank vacuum and capillary head effect should not exceed 9 psi (300 mmHg)
absolute
Figure 2-8 Remote Seal mounting