Process Insertion
Universal I/O
Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide 29
February 2013
3.3 Universal I/O
STUW700 – Three inputs (1-3) HLAI, (1-2) T/C, (1-2) Discrete Inputs
STUW 701 – Two inputs (1-2) HLAI, T/C, DI + One (1) Discrete Output
Connect wiring
Step Action
1
See Figure 3-8. Open the rear end cap (opposite end from display) by loosening the M3 locking
screw and unscrewing the end cap.
2
Open the cable gland (on right side below antenna). (Cable gland must be ordered as an option.)
3
Feed wiring (allowed diameter 6 to 8 mm) from other transmitter through the cable gland and
connect to terminal block using either voltage or current but not both. See wiring diagrams pages
30 and 31.
4
Plug battery connector into batteries.
5
Close rear end cap and cable gland.
6
Tighten M3 locking screw on the rear end cap.
Figure 3-8 Universal I/O Connection
To voltage/current source.
See wiring diagrams for all
models on pages 30 and 31.