3. Process Insertion
Universal I/O
32 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12
February 2013
TB1
TB2
1
2
3
4
5
6
STTW 500 MULTI-DI
CONNECTION
2 JUMPER WIRES
S1
S2
S3
NOTES:
1.
Shielded switch input cable is required for EMC conformity and is recommended for all
remote switch installations. The shield shall be grounded at the transmitter end only.
If the shield is grounded at the switch location, the shield shall not be connected at the
transmitter end.
2.
Jumper wires the same gauge and stranding as the switch wires are required for all
switch input combinations.
3.
Switches shall be isolated from each other and from earth ground to avoid common
mode noise problems.