78 Chapter 10 Communications
Searchline Excel™ Plus / Searchline Excel™ Edge – Technical Manual
Note 3 - Meaning of Detector detail status (bits derived from U8_OPRST_DETAIL_STATUS)
bit 0 Alarm1/Pre-alarm is active bit 8 Inhibit
bit 1 Alarm2/Alarm is active bit 9 Alarm0/Test signal1
bit 2 Overrange bit 10 Alarm3/Test signal2
bit 3 for future expansion bit 11 for future expansion
bit 4 Warning is active bit 12 for future expansion
bit 5 Fault is active bit 13 for future expansion
bit 6 for future expansion bit 14 for future expansion
bit 7 for future expansion bit 15 for future expansion
Note 4 - Definition of Measurement unit
0 invalid
12 flame detected bit
13 [dB] leak detected ultrasonically
14 [LEL.m] leak detected via open path infrared
15 to 255 for future expansion
Note 5 - Meaning of iInstID_Addr
Instrument MSByte LSByte
XNX 0x24 Modbus Address
XCD 0x25 Modbus Address
FSX Plus 0x26 Modbus Address
Searchline Excel
Plus & Searchline
Excel Edge
0x27 Modbus Address
Searchzone Sonik 0x28 Modbus Address
Note 6 - Definition of Relay configuration
bit num name def. val 0 - De-energized
1 - Energized
0 - Non-latching
1 - Latching
bit 0 Relay 1 Energized/De-energized 1
bit 1 Relay 2 Energized/De-energized 0
bit 2 Relay 3 Energized/De-energized 0
bit 3 Relay 1 Latch 0
bit 4 Relay 2 Latch 0
bit 5 Relay 3 Latch 0
bit 6 reserved
bit 7 reserved
bit 8 reserved
bit 9 reserved
6 to 15 unused in Searchline Excel Plus
or Edge