Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15
41
Operational Life
The pellistors fitted in the Flammable Catalytic sensors are poison resistant to maximize the
operational life of the sensor, however they can suffer from a loss of sensitivity when in the presence
of poisons or inhibitors, e.g. silicones, sulfides, chlorine, lead or halogenated hydrocarbons. A
typical operating life, subject to the presence of poisons/inhibitors is 36 months.
The NDIR (infrared) flammable gas sensor is not affected by the above-mentioned poisons and
therefore, has a longer life span. A typical operating life is 5 years.
The typical life of a toxic gas sensor is dependent on the application, frequency and amount of gas
exposure. Under normal conditions (3 monthly visual inspection and 6 monthly test/re- calibration), the
Sensepoint XCD Oxygen and other toxic sensors have an expected life equal to or greater than 24
months.
Refer to chapter 11.1 for sensor replacement procedures.