EasyManua.ls Logo

Honeywell Sensepoint XCD - Electrical Connections

Honeywell Sensepoint XCD
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15
19
5. Electrical connections
WARNINGS
Sensepoint XCD is designed for installation and use in Zone 1 or 2 hazardous areas in many countries
including Europe and Class 1 Division 1 or 2 area applications in North America.
Installation must be in accordance with the recognized standards of the appropriate authority in the
country concerned.
The transmitter has a potential electrostatic charging hazard. To minimize the risk of electrostatic
discharge:
• Ground the transmitter adequately
• Install the transmitter in a manner that will prevent accidental electrostatic discharges, e.g. ensure
that objects do not rub against the housing etc.
• Clean the enclosure with a damp cloth when necessary
Access to the interior of the detector, when carrying out any work, must only be conducted by trained
personnel.
Before carrying out any work ensure local regulations and site procedures are followed.
Appropriate standards must be followed to maintain the overall certification of the detector.
Care should be taken when removing and refitting the Sensepoint XCD Sensor Cartridge to the Sensor
Socket so that damage to the connection pins can be avoided.
For installations where conduit is used, and the sensor is mounted directly to the Sensepoint XCD,
there must be a Seal Fitting installed for each of the cable gland entries within 18 inches of the
Sensepoint XCD. The total distance of the location of these Seal Fittings is 18 inches. (e.g. If all 3 gland
entries are to be used, 3 Seal Fittings should be located, each within 6 inches of the wiring entrance).
If using an anti-seize compound, the threads should be thinly coated with an approved silicone free
compound e.g. petroleum jelly.
To reduce the risk of ignition of hazardous atmosphere, de-classify the area or disconnect the
equipment from the supply circuit before opening the detector enclosure. Keep assembly tightly closed
during operation.
Never attempt to open a junction box/enclosure or replace/refit the sensor in potentially hazardous
atmospheres while power is still applied to the transmitter.
The detector must be earthed/grounded for electrical safety and to limit the effects of radio frequency
interference. Earth/ground points are provided inside and outside the unit. Ensure that all
screens/instrument earth/clean earth wiring is earthed/grounded at a single point (either at the
controller or detector - BUT NOT BOTH) to prevent false alarms due to earth/ground loops.
Take care when handling sensors as they may contain corrosive solutions.
Do not tamper with or in any way disassemble the sensor.
Do not expose to temperatures outside the recommended ranges.
Do not expose sensors under storage conditions to organic solvents or flammable liquids.
At the end of their working life, replacement electrochemical sensors for oxygen and toxic gas must be
disposed of in an environmentally safe manner. Disposal should be according to local waste
management requirements and environmental legislation.
Alternatively, old replaceable sensors may be securely packaged and returned to Honeywell Analytics
clearly marked for environmental disposal.
Electrochemical sensors should NOT be incinerated as this action may cause the cell to emit toxic
fumes.
Refer to the local or national regulations relative to the installation at the site. For Europe see EN60079-
29-2, EN60079-14, EN45544-4 and EN61241-14.

Other manuals for Honeywell Sensepoint XCD

Related product manuals