Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15
45
Faults and Warnings
The table below provides details of possible error.
The unit has not been calibrated for the
configured calibration interval Calibration is
necessary due to change
of sensor/gas type
Transmitter Temperature limits
exceeded
Use ‘
✓
’ to clear when within limits
Alarm setting needs to be
configured
Re-configure alarm settings such that upper
alarm should not exceed user
configured scale
Use ‘
✓
’ to clear when within limits
The sensor is switched off to
prevent it from being
deteriorated
Make sure that there is no flammable
gas in the air and use ‘
✓
’ to clear when
within
limits
Cycle power to detector. Replace detector
For Toxic, replace sensor
For Flammable/IR, cycle power to detector.
Replace sensor
Reset transmitter. If fault still appear, replace
transmitter
Reset transmitter. If fault still appear, replace
transmitter
Reset transmitter. If fault still appear, replace
transmitter
Reset transmitter. If fault still appear, replace
transmitter
Reset transmitter. If fault still appear, replace
transmitter
Reset transmitter. If fault still appear, replace
transmitter
Check load resistor or sink/source mode
switch was configured properly
Reset transmitter. If fault still appear, replace
transmitter
Check supply voltage. Replace detector
Table 5 Fault and Warning List
Note: W-04 and W-05 are only for flammable catalytic bead sensors. For other gases, gas reading will
blink on the LCD instead of the over-range warning.