Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15
26
6. Default configuration
The Sensepoint XCD transmitter is supplied with the following default configuration.
Automatic according to Sensor
type connected
Sensepoint XCD recognizes the sensor cartridge
according to the gas type within its own sensor family
i.e. mV, EC or O2.
Fault (refer to table 5 chapter 11.3 for details)
2.0 mA or 4.0 mA (17.4mA)
Inhibit (during configuration/user settings)
For Oxygen, 2.0 mA or 17.4 mA
Value is sensor dependent
Contact Normally Open (NO)
Value is sensor dependent
Contact Normally Open (NO)
Contact Normally Open (NO)
2.0 mA (default) or 4.0 mA for
Toxic and Flammable
2.0 mA (default) or 17.4 mA
For Oxygen
Signal output inhibited during menu use.
If any relay is set to inhibit relay, then inhibit relay will
be activated.
No inhibit timeout. The detector waits for a button
press before returning to the previous state/setting.
Timeout period can be set in ‘Configure Inhibit’ menu
in Configuration Mode.
0000 (Password disabled). If changed then password
is activated.
Optional feature to identify the location or User’s
‘Tag’ number of the XCD
User selectable between
o
C or
o
F
ID, baud rates and Parity bit
ID: 1
Baud rates: 19,200
Parity bit : EVEN
Gas reading is zero if it is within deadband range
Table 3 Default configuration
* Alarm relays automatically reset when reading falls within alarm thresholds. If relay configured to
LATCH, then relays must be reset using the Magnetic Wand.
** Fault state (fault relay and analogue output <1 mA) is always non-latching.