6.13 Verifying Flow Configuration
Verify Flow
Configuration
To verify the SMV transmitters PV4 calculated flow output for your
application, you can use the SMV to simulate PV input values to the
transmitter and read the PV4 output. The output can be compared with
expected results and then adjustments can be made to the configuration if
necessary.
See Section 7.4, Using Transmitter to Simulate PV Input for the
procedure.