Alerts 37
AlarmPriority_HumSens Analog
Value
2082 {BIT0=INACTIVE,
BIT1=HIGH,
BIT2=MEDIUMN_ONBOARD,
BIT4=MEDIUMN_SYLK}
High Priority:
1. Only local sensor
configured & on-board
humidity sensor is in
alarm
2. Only Remote sensor
configured & TR40 sensor
connected to Sylk address
2 is giving null value and
digital output is
configured for
Humidification and
Dehumidification.
3. Configured as multi
sensor & both the remote
sensor & on-board
configured sensor has
failed.
Medium priority:
1. Configured as Multi
sensor & only the on-
board sensor has failed.
but getting reliable value
from the sylk sensors.
2. Configured as multi
sensor & only the sylk
sensor has failed with
values available from on-
board sensor.
When a valid network
humidity is available, then
the high priority alarms
will be considered as
medium priority alarm.
Alarm_SylkCommFailure Multistate
Value
2036 enum{Normal=1,
SylkAddr2Fail=2,
SylkAddr3Fail=3,
SylkAddr4Fail=4,
SylkAddr5Fail=5,
SylkAddr10Fail=10,
ManySylkFail=16}
Sylk communication
failure alarm. If more than
one Sylk sensor has failed,
then ‘ManySylkFail’ alarm
would be generated &
installer has to check the
BACnet points related to
all Sylk sensors to
understand which sensor
has failed.
Table 8 Alerts (Continued)
Name
BACnet
Object
Type
BACnet
Object
Instance
Range Description