38 Alerts
AlarmPriority_SpcTempHI_Loli
mit
Analog
Value
2084 {BIT0=INACTIVE,
BIT1=HIGH,
BIT2=MEDIUMN_ONBOARD,
BIT3=MEDIUMN_REMOTE,
BIT4=MEDIUMN_SYLK}
High priority: All space
temperatures are out of
range. No other resource
can be used.
Medium priority: Some of
the space temperatures
are out of range, other
resource can be used for
controlling.
AlarmPriority_DATempAlarm_F
ault
Multistate
Value
2029 enum{
Inactive=1,
Medium=2,
High=3}
High priority: Discharge
air sensor failure.
Medium priority:
Discharge air sensor out
of range.
Alarm_PipeSensorFailure Multistate
Value
2030 enum{
Inactive=1,
Active=3}
Pipe sensor failure occur.
Alarm_PipeSensorTempHeatOr
CoolThreshold
Analog
Value
2085 {Inactive=0, Active=1} For 2 pipe single coil heat
& cool: water temperature
is not suitable for heating/
cooling.
Alarm_RoomTempTrendFailure Binary
Value
2051 Inactive=0,
Active=1
Room temperature
changing trend is reversed
with system operating
mode.
Alarm_CHWDrainPanSensor Binary
Value
2052 Inactive=0,
Active=1
Alarm occurs when
condensation leak alarm/
pan drain sensor alarm
detects
Alarm_PipeSensorOutofRange Multistate
Value
2031 enum{Inactive=0, Active=1} Pipe sensor temperature
out of range.
Table 8 Alerts (Continued)
Name
BACnet
Object
Type
BACnet
Object
Instance
Range Description