54 Equipment configuration
4 - CONFIGURATION
If Output is set to 2-10 Vdc
- Heating Rage: 2.0-5.7 Vdc
- Cooling Range: 6.3-10.0 Vdc
- Off voltage is 6.0 Vdc
2-Pipe Single Coil
3. Tap 2-Pipe Single Coil.
The 2-Pipe Single Coil screen appears.
Table 21: 2-Pipe single coil
Heating/Cooling type Controls Options Description
Changeover Pipe sensor Set the pipe sensor as input value for
changeover method.
Network Input Set the network input as input value for
changeover method.
Changeover
Switch
Set the digital input as input value for
changeover method.
Heat & Cool On/Off Normally closed
• Set Valve output type as N.C
Normally open
• Set Valve output type as N.O
Floating
• Set output type Direct or Reverse
• Set Valve run time
• Set Min position when enabled
• Enable sync at mid night
Modulating Control
• Set min output when enabled
• Use Stage 1 as enable
Setting
• Set output type Direct or Reverse
• Set Min output of Modulating
valve
• Set Max output of Modulating
valve
Heat only On/Off Normally closed
• Set Valve output type as N.C
Normally open
• Set Valve output type as N.O
Floating
• Set output type Direct or Reverse
• Set Valve run time
• Set Min position when enabled
• Enable sync at mid night
Modulating Control
• Set min output when enabled
• Use Stage 1 heat as enable
Setting
• Set output type Direct or Reverse
• Set Min output of Modulating
valve
• Set Max output of Modulating
valve