EasyManuals Logo

Honeywell Unitary User Manual

Honeywell Unitary
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS
31-00610-01 24
BACNET™ IP CONTROLLER
Every Unitary controller has a physical MAC address
printed on the device. The physical MAC address of the
controller is listed using the "arp -a" function on the
command prompt of a Windows computer.
Connecting to an IP network
Honeywell Unitary controllers communicate over wired
IPv4 network using Ethernet connection via two RJ45
ports.
DHCP IP Configuration
A new controller from the factory has DHCP enabled by
default.
For the first 15 seconds after powering the controller,
a search for a DHCP server will be performed to
acquire an IP address.
Link-local addressing
If a DHCP server is not found, the controller will
switch to Auto IP mode, in which it follows link-local
addressing for address resolution.
It will acquire an IP address in the range 169.254.1.0
- 169.254.254.254. The controller will use the last
two characters of its serial number as the last octet
for starting address search. For example, if the serial
ends with “36” (decimal value= 54), the IP address is
set to 169.254.1.54).
The controller will periodically (every 1 minute)
search for the DHCP server. If a server is found, the
controller will acquire a new IP address from the
server and start using it immediately.