EasyManua.ls Logo

Honeywell Unitary - Modbus Considerations

Honeywell Unitary
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS
31 31-00610-01
Modbus Considerations
The RS-485 interface suitable for Modbus
communication is 2-wire with shield non-isolated,
hence the following considerations apply:
Maximum Modbus length (“L”):
4000 feet (1200 meters) for 9.6 – 78.8 kbps or
2600 feet (790 meters) for 115.2 kbps. It is
recommended that you select a low baud rate (for
example, 19.2 kbps) for reliable operation.
Use only shielded, twisted pair of cables and daisy
chain topology.
Ground noise should not exceed the EIA-485
common mode voltage limit.

Table of Contents

Related product manuals