Honeywell VISTA-128BPT - Using an RF Transmitter Zone; Control of Lighting and Appliances; Stand Alone Access Control

Honeywell VISTA-128BPT
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
SECTION 2: PROGRAMMING
U
U
s
s
i
i
n
n
g
g
a
a
n
n
R
R
F
F
T
T
r
r
a
a
n
n
s
s
m
m
i
i
t
t
t
t
e
e
r
r
Z
Z
o
o
n
n
e
e
A button type RF transmitter (5834-4) can be used to
provide access or egress for up to 4 doors. One
button will control one door. Also, a button can be
used to provide access or egress due to a panic or
duress condition.
To program the RF transmitter for access control,
perform the following steps:
1.
Enter Zone Programming in the #93
Menu Mode.
2.
Program the zone with a response type
27 (Access Point).
3.
Enter the access point number (00-31) of
the door.
4.
Indicate whether RF device is for entry or
exit.
5.
Enter the partition number
6.
Enter the input type: button RF (03).
7.
Enter the loop number.
8.
Enroll the serial number
See Zone Programming in the Programming Guide for
a detailed explanation.
RF buttons and pendants must be
assigned to a user number in order to
function. See SECTION 9: User Access
Codes for the procedure.
An RF transmitter will not provide access
or grant if the system is in any test mode.
C
C
o
o
n
n
t
t
r
r
o
o
l
l
o
o
f
f
L
L
i
i
g
g
h
h
t
t
i
i
n
n
g
g
a
a
n
n
d
d
A
A
p
p
p
p
l
l
i
i
a
a
n
n
c
c
e
e
s
s
Lighting and appliances can be controlled when an
access or exit event occurs. Lights or appliances can be
automatically turned on or off when a valid entry or egress
request is presented at an access point. To control these
devices, the control’s relays or the ACS relays or triggers
are used with keypads and/or RF transmitters whose
response type is Access Point (27). To program the
control of lighting and appliances, perform the following
steps:
1.
Enter Output Programming in the #93
Menu Mode.
2.
Program all the information for the relay.
3.
Select the output type: ECP (1) (4204).
See Output Programming in the Programming Guide for a
detailed explanation.
S
S
t
t
a
a
n
n
d
d
-
-
A
A
l
l
o
o
n
n
e
e
A
A
c
c
c
c
e
e
s
s
s
s
C
C
o
o
n
n
t
t
r
r
o
o
l
l
The control can be used for access control without
interfacing to VistaKey. A user can trigger an access point
(i.e., door strike) for 2 seconds by entering User Code + [0].
To program the control for Stand-Alone access control,
perform the following steps:
1.
Enter Output Programming in the #93
Menu Mode.
2.
Program the output type as 1, or 2.
3.
For type 1, program the ECP address and
relay number.
4.
For type 2, program the house and unit
codes.
5.
Program the relay number in field 1
76
(partition-specific).
See Output Programming in the Programming Guide for a
detailed explanation.

Table of Contents

Other manuals for Honeywell VISTA-128BPT

Related product manuals