VISTA-128BPT/128BPT-SIA/250BPT PROGRAMMING GUIDE
O
O
u
u
t
t
p
p
u
u
t
t
(
(
R
R
e
e
l
l
a
a
y
y
)
)
PROMPT EXPLANATION
DEVICE ADDRESS
Enter the device address of the relay module (4204) device.
Press [] to accept entry.
01 DEVICE TYPE
OUTPUT DEVICE 04
Enter the device type of 04 “Output Device”.
Press [] to accept entry.
O
O
u
u
t
t
p
p
u
u
t
t
P
P
r
r
o
o
g
g
r
r
a
a
m
m
m
m
i
i
n
n
g
g
The control supports up to 96 outputs. Outputs can be used to perform many different functions and actions. Each
output is defined as follows:
ACTIONS Defines how the device (relay) reacts to a command from the Start and Stop events.
START Defines the starting event that activates the action using a Zone Type, and/or Zone List, and/or Zone
Number.
STOP Defines the event that deactivates the output (changes the state of the action) using a Zone List
and/or Zone Type
The options used to start and stop these devices are described below, followed by the actual screen prompts and
available entries.
The letter(s) in parentheses after each function described below, such as (A) after ACTION, are those that appear in the
various summary displays of programmed data during programming.
S
S
u
u
m
m
m
m
a
a
r
r
y
y
S
S
c
c
r
r
e
e
e
e
n
n
Start Screen
01 A EV ZL ZT P
STT 0 0 00 00 0
A = Action E = Event ZL = Zone List
ZT = Zone Type P = Partition
Stop Screen
01 A ZL ZT P
STOP 0 00 00 0
A = Action E = Event ZL = Zone List
ZT = Zone Type P = Partition
ACTION (A) Refers to the action (listed below) in which the device will respond when it is activated by the "START"
programming.
There are five different action choices:
CLOSE for 2 SECONDS ....... Closes and resets after two seconds, no stop event is needed
STAY CLOSED .......................... Activates and remains active until stopped by some other event
PULSE ........................................... Continuous pulsing (one second on/one second off) until stopped by
some other event
NO RESPONSE ........................ The device is not used
TOGGLE ....................................... Activates (on) and deactivates (off) alternately with each activation of
starting event.
IMPORTANT: Do not program a stop parameter as this may cause
unpredictable results.