EasyManua.ls Logo

Honeywell VISTA-128BPT - Access Door Control

Honeywell VISTA-128BPT
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
VISTA-128BPT/128BPT-SIA/250BPT PROGRAMMING GUIDE
Z
Z
o
o
n
n
e
e
P
P
r
r
o
o
g
g
r
r
a
a
m
m
m
m
i
i
n
n
g
g
If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After
enrolling the transmitter, the battery need not be removed (except in a high traffic environment). This is
to prevent enrolling the wrong serial number.
PROMPT EXPLANATION
ZONE PROG?
1 = YES 0 = NO 0
Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [] to display the next
screen. Press # to display a previous screen.
SET TO CONFIRM?
1 = YES 0 = NO 0
This prompt appears once upon entering Zone Programming Mode.
If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been
entered later.
ENTER ZONE NO.
000 = QUIT 010
Zone 010 entered
Enter the 3-digit zone number to be programmed, as follows:
Protection Zones .................................... 001250
Relay Zones .............................................. 601632
ECP Device Supervisory Zones ...... 800830
System Supervisory Zones ............... 970 (bell supervision), 988, 990 (RF receiver), 992 (duress), 997
(polling loop short)
Keypad Panic Zones ............................ 995, 996, 999
UL
WHEN SUPERVISING THE BELL OUTPUT (ZONE 970), ONLY ONE DEVICE CAN BE
CONNECTED TO THE ALARM OUTPUT (TERMINALS 4 AND 5) FOR UL AND FIRE
INSTALLATIONS.
Press [] to continue.
010 ZT P RC In L
00 1 10 00 1
This display appears, showing a summary of the zone's current programming.
ZT = Zone Type,
P = Partition,
RC = Report Code,
In = The input type of device, and
L = The device's loop number to which the sensor is connected.
NOTES:
Some devices can support more than one zone by means of individual loops (for example, 5834-4,
5816, 5817, etc.).
If the zone is not programmed, the display appears as shown here.
If you are checking a zone's programming, and it is programmed satisfactorily, press [#] to back up
one step and enter another zone number, if desired.
Press [] to continue.
010 ZONE TYPE
PERIMETER 03
Zone number 010 and
Zone Type 03 entry shown
These are special zone
types used with 5800
Series Wireless Keys
Units that result in
arming the system in
the STAY or AWAY
mode, or disarming the
system, depending on
the selection made.
Each zone must be assigned a zone type, which defines the way in which the system responds to faults
in that zone. Refer to the Zone Type Definition section. Enter the zone type desired (or change it, if
necessary). Available zone types are listed below.
NOTE: If changing a zone type, make sure you delete the previous zone and reprogram the entire
zone.
00 = Assign for Unused Zones
12 = Not Used
01 = Entry/Exit #1, Burglary
14 = CO Detector Alarm
02 = Entry/Exit #2, Burglary
16 = Fire With Verification
03 = Perimeter, Burglary
20 = ArmSTAY†
04 = Interior Follower, Burglary
21 = Arm AWAY†
05 = Trouble Day/Alarm Night
22 = Disarm†
06 = 24 Hr. Silent Alarm
23 = No Alarm Response (e.g., relay activation)
07 = 24 Hr. Audible Alarm
27 = Access Point
08 = 24 Hr. Auxiliary
28 = Not Used
09 = Fire Without Verification
29 = Momentary Exit (used with VistaKey module)
10 = Interior Delay, Burglary
Press [] to continue.
010 Arm w/ Fault?
1 = YES 0 = NO 0
If you selected response type 1, 2, 4, or 10, this prompt appears.
Enter 1 = to enable arming of the partition with this zone faulted.
NOTE: The zone must be restored (see Force Arming, the next prompt) before the exit delay expires
otherwise the system starts the entry delay and must be disarmed, or an alarm occurs.

Table of Contents

Other manuals for Honeywell VISTA-128BPT

Related product manuals