VISTA-128BPT/128BPT-SIA/250BPT PROGRAMMING GUIDE
S
S
c
c
h
h
e
e
d
d
u
u
l
l
i
i
n
n
g
g
P
P
r
r
o
o
g
g
r
r
a
a
m
m
i
i
n
n
g
g
F
F
i
i
e
e
l
l
d
d
s
s
Fields 205 - 211 are required to program Open (Disarm) and Closing (Arming) schedules.
The control can auto arm/disarm at a predetermined time using Open/Close or Timed Events Schedules. Refer to the
Installation and Setup Guide for detailed information.
FIELD TITLE and DATA ENTRIES Default Values
2
05
Auto-Arm Delay (partition-specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto arming.
[15] A | E
This is the time between the end of the arming window and the start of auto-arm warning time (field 206).
UL
MUST BE SET TO 0 FOR UL INSTALLATIONS
2
06
Auto-Arm Warning Period (partition-specific)
01-15 times 1-minute warning.
00 = no warning period.
[15] A | E
This is the time that the user is warned by a keypad sounding and display to exit the premises prior to auto arming of the
system.
UL
MUST BE SET TO 0 FOR UL INSTALLATIONS
2
07
Auto-Disarm Delay (partition-specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto disarming.
[15] A | E
This is the time between the end of the disarming window and the start of auto disarming of the system.
UL
MUST BE SET TO 0 FOR UL INSTALLATIONS
2
08
Force Arm Enable for Auto-Arm (partition-specific)
0 = disable
1 = enable
[0] A E
Enabled: System automatically bypasses any faulted zones when it attempts to auto-arm.
Disabled: System will not auto-arm if zone is faulted.
ULC
FORCE ARMING IS NOT A ULC LISTED FEATURE AND MUST BE DISABLED FOR ULC
INSTALLATIONS.
2
09
Open/Close Reports by Exception (partition-specific)
0 = disable
1 = enable
[0] A E
Enabled: Open/Close reports only send if the openings/closings occur outside the arm and disarm windows.
NOTES:
Open reports are also suppressed during the closing window in order to prevent false alarms if the user arms the
system, then re-enters the premises, for example to retrieve a forgotten item.
Openings and closings are still recorded in the event log.
2
10
Allow Disarming Only During Arm/Disarm Windows
(partition-specific)
0 = disable
1 = enable
[0] A E
Enabled: Disarming of the system is allowed only during the arming/disarming windows, or if the system is in alarm (if
211 is set to 1).
NOTES:
This applies only to Operator-level users. Installer, Master, and Manager-level users can disarm the system at any
time.
Duress users behave the same way as Operator-level users.
2
11
Allow Disarm Outside Window if Alarm Occurs
0 = disable
1 = enable
[0] A E
Enabled: Allows the system to be disarmed outside the programmed disarm (opening) window if an alarm has occurred.
Otherwise disarming is allowed only during the disarm window.
Used only if field 2
10 is enabled.