35
SECTION 3: DATA FIELD DESCRIPTIONS
FIELD TITLE and DATA ENTRIES Default Values
2
18
Enable GOTO for this Partition (partition-specific)
0 = disable
[1] A E
Enabled: Selected partition can be accessed from another partition’s keypad using the GOTO command.
• User must be programmed as a multi-access user.
• Press their code + ∗ + partition # to switch partitions.
• Press their code + ∗ + 0 to switch back to the keypads home partition.
• Time out after two minutes of no keypad activity.
2
19
Use Partition Descriptor
0 = disable
[0] A E
Enabled: Normal keypad display will include a partition number and four-digit descriptor.
2
22
Display Fire Alarms of Other Partitions (partition-
specific)
0 = disable
[0] A E
If enabled, allows fire alarms that occur on other partitions to be displayed at this partition’s keypad(s).
2
23
Display Burg, Panic and CO Alarms for Other Partitions
(partition-specific)
0 = disable
[0] A E
If enabled, allows burglary, panic and CO alarms that occur on other partitions to be displayed at this partition’s keypad(s).
2
24
Display Troubles of Other Partitions (partition-specific)
0 = disable
[0] A E
If enabled, allows troubles that occur on other partitions to be displayed at this partition’s keypad(s).