58
VISTA-128BPT/128BPT-SIA/250BPT PROGRAMMING GUIDE
D
D
e
e
v
v
i
i
c
c
e
e
P
P
r
r
o
o
g
g
r
r
a
a
m
m
m
m
i
i
n
n
g
g
This menu is used to program keypads, receivers, and relay modules, etc.
Device Address
00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression
options, and these settings cannot be changed.
From Data Field Programming mode, press #93 to display "ZONE PROG?" Press [0] repeatedly to display "DEVICE
PROG?"
PROMPT EXPLANATION
DEVICE PROG?
1=YES 0=NO 0
Press [1] to enter Device Programming.
DEVICE ADDRESS
01-30, 00=QUIT 01
The device address identifies the device to the control. Enter the 2-digit device address number to
match the device's physical address setting (01-30).
NOTE: Device Address 01 is defaulted for an alpha keypad with Keypad Global arm/disarm disabled.
Press [] to accept entry.
DEVICE TYPE
00
Select the type of addressable device as follows:
00 = device not used
06 = Communications device
01 = alpha keypad (6160, graphic/touch-
screen)
08 = Not Used
03
= RF receiver (5881)
09
= Not Used
04
= output relay module (4204)
10
=
Not Used
05
= Not Used 12 = Remote Interactive Service (RIS)
Press [] to accept entry.
A
A
l
l
p
p
h
h
a
a
K
K
e
e
y
y
p
p
a
a
d
d
PROMPT EXPLANATION
01 CONSOLE PART.
1
If you selected device type 01 (alpha keypad or touch screen keypad), this prompt appears. Enter the
addressable device's default partition number (01 to maximum number of partitions programmed for
system in field 200). This is the primary partition for the device. Enter 9 to make this keypad a "Master"
keypad for the system.
Press [] to accept entry.
01 SOUND OPTION
0
Keypads can be individually programmed to suppress arm/disarm beeps, entry/exit beeps and chime
mode beeps. This helps prevent unwanted sounds from disturbing users in other areas of the premises.
Enter a number 0-3 for the keypad sounding suppression options desired for the keypad as follows:
0 = no suppression
1 = suppress arm/disarm & entry/exit beeps
2 = suppress chime mode beeps only
3 = suppress arm/disarm, entry/exit and chime mode beeps
Press [] to accept entry.
01 KEYPAD GLBL?
0
Each keypad can give users with access to multiple partitions the ability to arm and disarm those
partitions from it. To enable this keypad for global arming/disarming, enter 1. To prevent the ability to
use this keypad for global arming/disarming, enter 0.
Press [] to accept entry.
01 AUTO-STAY ARM
DISABLED? 0
0 = No, 1 = Yes. If enabled (1=yes), Auto-Stay Arming is turned off for the selected keypad address
(system does not automatically revert to Auto-Stay Arm mode if armed Away and no entry/exit doors are
opened).
Default is No.
Press [
] to accept entry.
01 AUI ?
1 = YES 0 = NO 0
If you selected device type 01 (alpha keypad), this prompt appears. Enter 1 (YES) if the device is a
graphic/touch-screen keypad.
Press [] to accept entry.