64
VISTA-128BPT/128BPT-SIA/250BPT PROGRAMMING GUIDE
PROMPT EXPLANATION
02 START EVENT
NOT USED 0
An output may be activated by an Event/Zone List or Zone Number combination, and/or by a Zone
Type/System Operation. For an Event/Zone List or Event Zone Number combination, enter the event
code as follows:
0 = Not used 3 = Fault
1= Alarm 4 = Trouble
If you are not using a Zone List or Zone Number to activate the relay, enter 0.
Press [∗] to continue.
02 START: ZN LIST
00
A zone list is a set of zones that can be used to initiate the start or stop relay action. If a zone list is being
used to start this relay action, enter the zone list number, 1-15. If a zone list is not being used, enter 0.
Press [∗] to continue.
02 START: ZONE #
000
A specific zone can be used instead of or in addition to an Event/Zone List or Zone Type/System
Operation combination to start the relay action. Enter the 3-digit zone number.
Additional Output Programming Notes when using with a Burglary/Panic Zone Type:
1. When using a START EVENT OF FAULT on a ZONE # and no other start or stop entries, the Output
assigned to the relay will follow the zone (tripped Relay on, restored Relay off) on
FAULT/ALARM/TROUBLE, armed and disarmed.
2. When using a START EVENT OF FAULT on a ZONE # and a STOP ZONE/TYPE of 22, the Output
assigned to the relay will START on FAULT/ALARM/TROUBLE, but will not Stop until code and off
is entered.
3. When using a START EVENT OF ALARM on a ZONE # and no other start or stop entries, the
Output assigned to the relay will follow the zone (on after an ALARM only) and off when zone
restores.
4. When using a START EVENT OF ALARM on a ZONE # and a STOP ZONE/TYPE of 22, the Output
assigned to the relay will START only on ALARM of the zone and will not Stop until code and off is
entered.
NOTE: BYPASSING A ZONE WILL PREVENT IT FROM STARTING AN OUTPUT.
Press [∗] to continue.
02 START: ZN TYPE
NO RESPONSE 00
A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List combination
or a specific zone to start the relay action. If a Zone Type/System Operation is being used, enter the 2-
digit code as listed in the table that follows.
Refer to the notes in Start ZONE # prompt. For detailed Zone Type Descriptions, refer to page 2-9.
Choices for Start/Stop Zone Types and System Operations:
00 = No Response (Not Used)
27 = Access Point (allows more than one
relay to be controlled by activation if
access point request)
43 = Communication failure
45 = Polling Loop Failure
04 = Interior Follower 28 = Not Used 47 = Console Failure
05 = Trouble Day/Alarm Night 29 = Momentary Exit 51 = RF Receiver Failure
09 = Fire Alarm or Trouble
34 = Code + [#] + 71 Key Entry
56 = XX Minutes (enter XX in field 1∗74) *
10 = Interior W/Delay 35 = Code + [#] + 72 Key Entry
57 = YY Seconds (enter YY in field 1∗75) *
37 = 2 Times Bell Timeout **
60 = Audio Alarm Verification (must be
selected for both START and STOP
operation)
16 = Fire With Verification
22 = Disarming (Code + Off)
* Stop condition only
** Or at disarming, whichever occurs earlier
*** The output also activates when the partition is armed in the INSTANT mode
**** The output also activates when the partition is armed in the MAXIMUM mode
If you are using options 56 and/or 57 (usually as the STOP Zone Type), you must program data fields 1
∗74 and 1∗75
respective relay timeouts for minutes and seconds.