33
SECTION 3: DATA FIELD DESCRIPTIONS
FIELD TITLE and DATA ENTRIES Default Values
2
00
Number of Partitions
Enter 1-8.
[1] A E
Enter the number of partitions used in the system.
2
01
Daylight Saving Time Start/End Month
0 = disable
[03, 11] A | E AA | E
Enter the months (00-12) in which daylight saving time starts and ends.
Enter 00, 00 if daylight saving time does not apply to the user’s region.
Standard setting for U.S. is 03,11.
2
02
Daylight Saving Time Start/End Weekend
0 = disable
1 = enable
[2, 1] A
EStartE
A
A
EEndE
Enter the start and end weekends for daylight saving time as follows:
2 = Second
3 = Third
6 = Next to last
7 = Third from
Standard setting for U.S. is 2, 1.
2
03
ULC S304 Enable
0 = disable
[1] A E
Enabled:
• A 2-minute stabilization upon power up – (zones scanning will be disabled when the panel is powered up for 2
minutes).
• Previous reporting will be enabled:
NOTE: If there is a phone line (or radio) failure and the panel has exhausted its maximum attempts to send
reporting events to the central station, the panel will hold the messages in a buffer and resend upon restoral
of the communication path. In addition, old messages that are sent will indicate that they are not current
messages so that the central station does not dispatch on them. In order to accomplish this, an event
qualifier of “6” will be sent in place of the “1” or “3” character in the message. The “6” indicates that the
message is old. Events will be sent in chronological order and will be time-stamped in the system’s event log
.
• Attempting to arm when there is a faulted burglary zone will cause a 4-second long tone.
ULC
THE ULC S304 ENABLE MUST BE SET TO “1” (ENABLED) FOR ULC INSTALLATIONS.