SECTION 3: DATA FIELD DESCRIPTIONS
START (STT) Determines when and under what conditions the device is activated. The following START options are
available:
1) EVENT (EV)
The condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone list) in order
to activate the device. These conditions apply only when a zone list or zone number is used.
The different choices for "EVENT" are listed below and in “Programming Relays” later in this
section.
ALARM .......................... Action begins upon any alarm in an assigned zone in the zone list
FAULT ............................ Action begins upon any opening of an assigned zone in the zone list
TROUBLE .................... Action begins upon any trouble condition in an assigned zone in the zone
list
2) ZONE LIST (ZL)
Group of zones to which the “EVENT” applies in order to activate a particular device.
NOTES:
• Any zone type can be used in a Zone list EXCEPT 20, 21, and 22
• There are a total of 15 zone lists that can be programmed
• When the selected EVENT (alarm, fault or trouble) occurs on any zone in the
selected “Start” ZONE LIST (01-15), activation of the selected device will START.
To start an Output you must also select the “EVENT” in order to activate a particular device.
3) ZONE #
A specific zone going into alarm, fault, trouble, or restore (Event programming) can be used to start
the relay action. Enter the 3-digit zone number (001-250).
4) ZONE TYPE/SYSTEM OPERATION (ZT)
This start parameter is used if activation is desired by all zones within a specific Zone Type, this
may be used in place of a “ZONE LIST” and “EVENT.” Example, if an activation is desired for any
Fire zone, then a Zone Type of 39 “Any Fire Alarm” is entered.
NOTES: If a system operation, such as “DISARMING” or “ANY FIRE ALARM,” is to activate the
device, enter the appropriate choice under the “ZONE TYPE” option.
• The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the
“EVENT/ZONE LIST” combination.
• Any zone of the chosen response type in alarm, trouble, or faulted state will cause the device
to activate the selected action.
• If the same “ZONE TYPE” is also chosen for the STOP programming, any zone of that type
that restores will de-activate the device.
• If a "SYSTEM OPERATION" is chosen, that operation will cause the device to activate as
selected in "ACTION.” The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are
listed below:
Applies to the following Zone Types.
01 = Entry/ Exit #1 05 = Trouble Day/Alarm
Night
09 = Fire Alarm or Trouble
02 = Entry/exit #2 06 = 24-Hr. Silent 10 = Interior W/Delay
03 = Perimeter 07 = 24-Hr. Audible 14 = CO Detector Alarm
04 = Interior
Follower
08 = 24-Hr. Auxiliary 16 = Fire With Verification
Refers to the Zone
Types above
Alarm, trouble, or fault will cause the
device to activate
A restore of any zone with this zone type
will de-activate the device.
20 = Arming-STAY Code + 3 or 7 (INSTANT) mode.
21 = Arming-AWAY Code + 2 or 4 (MAXIMUM) mode. Do not have to change state
22 = Disarming Any code + 1, regardless of armed state.
23 = No Alarm
Response
Alarm, trouble, or fault will cause the
device to activate
A restore of any zone with this zone type
will de-activate the device.
NOTE: EVENT OF FAULT MUST BE SELECTED WHEN STARTING ON A ZONE