VISTA-128BPT/128BPT-SIA/250BPT PROGRAMMING GUIDE
FIELD TITLE and DATA ENTRIES Default Values
1
22
Cross Zoning Pair One
Enter 001-250
[000, 000] A | | E AA | | E
Select the first pair of cross zones, which must both be faulted within a 5-minute period to cause an alarm.
Must be 000, 000 for UL installations.
1
23
Cross Zoning Pair Two
Enter 001-250
[000, 000] A | | E AA | | E
Select the second pair of cross zones, which must both be faulted within a 5-minute period to cause an alarm.
UL
Must be 000, 000 for UL installations.
1
24
Cross Zoning Pair Three
Enter 001-250
[000, 000] A | | E AA | | E
Select the third pair of cross zones, which must both be faulted within a 5-minute period to cause an alarm.
UL
Must be 000, 000 for UL installations.
1
25
Cross Zoning Pair Four
Enter 001-250
[000, 000] A | | E AA | | E
Select the fourth pair of cross zones, which must both be faulted within a 5-minute period to cause an alarm.
UL
Must be 000, 000 for UL installations.
1
26
Panic Button or Speedkey
For A, B, C keys:
00 = panic function
01-32 = macro number
For D key:
00 = to select a macro to execute when key is pressed
[00, 00, 00, 00] A
|
EAE
AA
|
EBE
AA
|
ECE
A
A
|
EDE
NOTE: For 128BPTSIA Panels ONLY, the default entry is
[01, 02, 03, 00].
Select for the A, B, and C keys whether the system performs a panic or a speedkey function when the key is pressed.
Select for the D key whether the system performs a specific macro or if the user will select a macro when the key is
pressed.
NOTES:
• If using the A, B, and C, keys for panic alarms, verify fields ∗22 and ∗85 are programmed correctly.
• If a user code with global arm/disarm is used to execute the macro, the user’s global capabilities will override any
arm/disarm commands in the macro sequence.
1
28
RF Transmitter Low Battery Sound
0 = disarmed state only
1 = both armed and disarmed states
[0] A E
Select when the RF transmitter low-battery condition should display and audible beep annunciate on the keypad.
UL
MUST 1 FOR UL INSTALLATIONS.
1
29
RF Transmitter Low Battery Reporting
0 = disable
[0] A E
If enabled, the system sends a Trouble message for RF transmitter low-battery condition to the central station.
The Trouble message will be sent for a transmitter supervision failure (E384), independent of this selection.
UL
MUST BE 1 FOR UL INSTALLATIONS.