87
SECTION 4: SYSTEM LAYOUT WORKSHEETS
A = DEVICE ACTION 0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off; 4 =
Toggle alternately between START and STOP events
EV = EVENT 0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble
ZL = ZONE LIST 01-15, 00 = Not Used
"START" ZONE LIST: Upon alarm, fault, trouble or restore of ANY zone in this list, device
action will START.
"STOP" ZONE LIST: Upon restore of ALL zones on this list, device action will STOP. It
need not be same list as used for START.
ZT = ZONE TYPE/SYSTEM OPERATION
Choices for Zone Types are:
00=zone not used 08=24-hour auxiliary 22=disarm
01=entry/exit 1 09=supervised fire 23=no alarm response
03=perimeter 12=Not Used 27=Not Used
04=interior (follower) 14=CO detector alarm 28=Not Used
05=day/night burglary 16=fire w/verification 29=momentary exit
06=24 hour silent 20=arm stay
NOTE: Any zone in "ZT" for Start, going into alarm, fault, or trouble will activate the relay.
Any zone in "ZT" for Stop, that restores will stop the relay action.
Choices for System Operation are:
00 = No Response (Not Used)
27 = Access Point (allows more than
one relay to be controlled by
activation if access point
request)
43 = Communication failure
45 = Polling Loop Failure
05 = Trouble Day/Alarm Night
09 = Fire Alarm or Trouble
34 = Code + [#] + 71 Key Entry
56 = XX Minutes (enter XX in field
1∗74) *
35 = Code + [#] + 72 Key Entry
16 = Fire With Verification
57 = YY Seconds (enter YY in field
1∗75) *
37 = 2 Times Bell Timeout **
22 = Disarming (Code + Off)
60 = Audio Alarm Verification (must be
selected for both START and
* Stop condition only
** Or at Disarming, whichever occurs earlier
*** The output also activates when the partition is armed in the INSTANT mode
**** The output also activates when the partition is armed in the MAXIMUM mode
P = PARTITION No. 1-8, 0 = Any
ZONE LISTS FOR OUTPUT DEVICES – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in
the required data on the worksheet below and follow the procedure shown earlier in this Programming Guide as you enter
the data during the displays and prompts that appear in sequence. Up to 15 zone lists may be created
NOTE: Record desired zone numbers below. More or fewer boxes than shown may be needed, as any list may include
any or all of system's zone numbers.
Zone List 1: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 2: Started or stopped by zone numbers (enter 000 to end entries).