EVERYDAY OPERATIONS XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8) 44
DIO Module Assignment
02 ? XLF521 0001FC234088
03 <Unassigned> 1
04 <Unassigned>
05 XFL524 0001FC234062
Modules that have been assigned have their module type and Neuron ID displayed
beside them. Special characters indicate the module status according to the
following key:
! An exclamation mark indicates that the module was previously assigned to this
controller in CARE but is now being used by another controller.
- A minus sign indicates that the module is assigned but not yet commissioned.
This is the default state after assignment.
? A question mark indicates that the module is assigned but not available or not
found during commissioning.
If no special character is seen alongside a module name, this indicates that the
module is correctly assigned and commissioned.
6. To change an assignment, select any line (module address) by using the arrow
keys to move to and highlight it and then pressing Enter (). Could also be done
with an assigned module.
RESULT: The display window lists the Distributed I/O module types.
DIO Module Assignment
Address: 04
None
XFL521 1
XFL522
XFL523
7. Select a module type, or None to clear a module assignment, by using the
arrow keys to move to and highlight it and then pressing Enter ().
RESULT: If None is selected, the display window lists the previous screen with
this module (here 04) marked as “<Unassigned>”. Module type and
Neuron ID are cleared.
If a specific type is selected, an intermediate mask is displayed, while
the controller searches on the L
ONWORKS network for all modules with
the specified module address and module type.
Please be patient, while
DIO Modules will be searched
After a brief period, the next screen is displayed. The display window
lists all modules of the same type and of the same address. The
search can be canceled by pressing Cancel (C).