SpecificationComponent
HPE Alletra 5000, 2120:
• 5010: 700 W
• 5010H: 500 W
• 5030: 800 W
• 5030H: 700W
• 5050: 950 W
• 2120: 400 W
HPE Nimble Storage HFxx, ES3:
• HF20: 700 W
• HF20C: 700 W
• HF20H: 500 W
• HF40: 800 W
• HF40C: 800 W
• HF60: 950 W
• HF60C: 950 W
• ES3: 400 W
• Startup: 8A @ 120V
• Startup: 4A @ 240V
CAUTION: Startup current draw may exceed 8A.
Power consumption (approxi-
mate)
HPE Alletra 5000, 2120:
• 5010: 2296 BTU/hr typical
• 5010H: 1968 BTU/hr typical
• 5030: 2788 BTU/hr typical
• 5030H: 2296 BTU/hr typical
• 5050: 3116 BTU/hr typical
• 2120: 984 BTU/hr typical
HPE Nimble Storage HFxx, ES3:
• HF20: 2296 BTU/hr typical
• HF20C: 2296 BTU/hr typical
• HF20H: 1968 BTU/hr typical
• HF40: 2788 BTU/hr typical
• HF40C: 2788 BTU/hr typical
• HF60: 3116 BTU/hr typical
• HF60C: 3116 BTU/hr typical
• ES3: 984 BTU/hr typical
Formula: Max wattage x .96 = Avg wattage x 3.412141633 = BTU/hr
BTU (estimate)
Installation of this equipment must comply with local and regional electrical regulations governing the installation of information
technology equipment by licensed electricians. This equipment is designed to operate in installations covered by Article 645
of the National Electrical Code and NFPA 75.
Hardware and Model Specifications 139
Documentation Feedback: doc-feedback-hpe-storage@hpe.com