UPS operations 44
Verifying the REPO port connection
N
OTE: While testing, operate connected equipment in a safe test mode so the effects do not
disrupt critical operations.
After connecting the REPO port (on page 20):
1. Initiate a REPO by closing the REPO contact.
The Self Test, Battery Fault, Site Wiring Fault, Overtemperature, Overload, and Utility LEDs flash.
C
AUTION: If the polarity is reversed while connecting the REPO port, the UPS powers up
normally.
2. Verify proper connection of the REPO port:
a. Power up the UPS ("Starting power to the load" on page 25).
b. Disconnect the REPO port.
c. Reconnect the REPO port.
If the polarity is correct, the REPO connectors can be disconnected, and then reconnected,
without initiating a REPO.
d. Verify that the UPS remains in Operate mode (on page 40).
e. If a REPO is initiated, the polarity is reversed. Check and correct the connections.
Powering down the UPS
1. Shut down all load devices.
2. Press the Off button to take the UPS out of Operate mode. Power to the load receptacles ceases.
The On Battery LED and Load Level indicator flash.
3. Disconnect the UPS from utility power.
4. Wait at least 60 seconds for the UPS internal circuitry to discharge.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE R/T3000 G2 and is the answer not in the manual?

HPE R/T3000 G2 Specifications

General IconGeneral
Power Capacity3000 VA
Battery TypeSealed Lead-Acid (SLA)
Output Power Capacity2700 Watts
Rack Height2U
Input Frequency50/60 Hz
Output Frequency50/60 Hz
EfficiencyUp to 95%
Operating Humidity0 to 95% non-condensing
Form FactorRack/Tower
InterfaceUSB, Serial
Product TypeUPS
Battery RuntimeVaries by load
Transfer Time4-6 ms
Operating Temperature0 to 40°C (32 to 104°F)
Warranty3 years
Nominal Output Voltage120 V, 208 V, 230 V
Noise Level40-50 dB