Obtaining new batteries
New batteries might be required within 30 to 60 days when the Battery Fault LED illuminates. Obtain
spare batteries for the UPS when this occurs.
Spare battery modules are available for this UPS. The UPS spare battery kit part number is 517703-001.
CAUTION: Because of the short shelf life of the batteries, avoid storing a battery spare as a
backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep
these batteries charged while in storage is implemented.
UPS battery replacement procedure
W
ARNING: To prevent personal injury from electric shock or damage to the equipment,
remove the battery lead labels, and verify that the ERM circuit breakers are in the Off position.
This component is hot-swappable and can be replaced without powering down the UPS.
1. (optional) To replace the component with the UPS powered down, refer to "Powering down the UPS
(on page 44)."
C
AUTION: When hot-swapping batteries, the UPS is not protected in the event of a utility
power failure.
2. Remove the UPS front bezel ("Removing the UPS front bezel" on page 45).
3. Disconnect the battery leads.
4. Remove the UPS battery bracket.
5. Remove the UPS battery modules.
I
MPORTANT: Do not pull the battery leads when removing or installing the batteries.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE R/T3000 G2 and is the answer not in the manual?

HPE R/T3000 G2 Specifications

General IconGeneral
Power Capacity3000 VA
Battery TypeSealed Lead-Acid (SLA)
Output Power Capacity2700 Watts
Rack Height2U
Input Frequency50/60 Hz
Output Frequency50/60 Hz
EfficiencyUp to 95%
Operating Humidity0 to 95% non-condensing
Form FactorRack/Tower
InterfaceUSB, Serial
Product TypeUPS
Battery RuntimeVaries by load
Transfer Time4-6 ms
Operating Temperature0 to 40°C (32 to 104°F)
Warranty3 years
Nominal Output Voltage120 V, 208 V, 230 V
Noise Level40-50 dB