Specifications 61
Power protection specifications
UPS model VA Nominal power
Nominal voltage
R/T3000 NA/JPN
Output tolerance specifications
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
±5% of nominal output voltage rating
Output feature specifications
Feature Specification
94% nominal input voltage
Sine wave; 5% THD with typical PFC load
Noise filtering
EN 55022 line filter for normal and common mode
use
Battery specifications
Type
12 V, 5 AH, sealed, maintenance-free, rechargeable, valve
regulated lead-acid batteries with a 3-5 year service life at 25°C
(77°F).
The battery modules have a battery string voltage of 120 V.
Charging
Complete charge takes no more than 48 hours. After
approximately 3 hours, the batteries reach 80% charge at
default nominal utility voltage and no load.