HPE R/T3000 G2 User Manual

HPE R/T3000 G2
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #55 background imageLoading...
Page #55 background image
Troubleshooting 55
Off
On
Off
On—Batt
ery
capacity
<25%
On—Batt
ery
capacity
>25%
On—Batt
ery
capacity
>50%
On—Batt
ery
capacity
>75%
Flashing
Overload condition (on page
58)—UPS power capacity is
exceeded while on battery
with no other faults
Off
On
Off
Off
Off
Off
Flashing
Flashing
Overload condition (on page
58)—UPS power capacity is
exceeded while on battery
with overtemperature fault
Off
Flashing
Off
Flashing
Flashing
Flashing
Flashing
Flashing
Unit is powering down
Flashing
Flashing
Flashing
Flashing
Flashing
Flashing
Flashing
Flashing
Checksum failure error (on
page 58)
* This LED can be in any state.
For the location of individual LEDs, see "UPS front panel LED indicators (on page 7)."
UPS is in Auto-Bypass mode
The UPS transfers from Operate mode (on page 40) to Auto-Bypass when one of the following fault
conditions is detected:
Inverter AC over voltage
Inverter AC under voltage
Rectifier input over current
Inverter output over current
Inverter fault
Heat sink over temperature
Fan failure
Overload
The load is supported, but not protected while in Auto-Bypass mode.
Action:
1. If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general fault condition, see the HPE Power Manager
user guide available for download from the Hewlett Packard Enterprise website
(http://www.hpe.com/info/rackandpower).
2. Verify that no blockage of airflow to the front bezel and rear panel exists.
UPS is in Converter Off mode
Fault conditions cause the UPS to transfer to Converter Off mode from Standby mode (on page 40) only.
If the UPS is powering the load, fault conditions cause the UPS to transfer to Auto-Bypass mode instead.
If a fault condition exist and the UPS is running in Auto-Bypass mode (on page 41), press the Off button to
transfer the UPS to Converter Off mode.
The load is not supported while in Converter Off mode.
The following fault conditions trigger Converter Off mode:
Inverter AC over voltage
Inverter AC under voltage

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE R/T3000 G2 and is the answer not in the manual?

HPE R/T3000 G2 Specifications

General IconGeneral
Power Capacity3000 VA
Battery TypeSealed Lead-Acid (SLA)
Output Power Capacity2700 Watts
Rack Height2U
Input Frequency50/60 Hz
Output Frequency50/60 Hz
EfficiencyUp to 95%
Operating Humidity0 to 95% non-condensing
Form FactorRack/Tower
InterfaceUSB, Serial
Product TypeUPS
Battery RuntimeVaries by load
Transfer Time4-6 ms
Operating Temperature0 to 40°C (32 to 104°F)
Warranty3 years
Nominal Output Voltage120 V, 208 V, 230 V
Noise Level40-50 dB