Shenzhen Hpmont Technology Co., Ltd. Chapter 7 Detailed Function Introduction
HD09-S Series User Manual V1.1 - 61 -
Ref. Code Function Description Setting Range [Default]
F17.06 Communication overtime action choice 0 - 3 [3]
Communication error action selection
F17.08 Communication external device fault action selection 0 - 3 [1]
F17.06 defines the protection action selection when communication timeout detection.
F17.07 defines the protection action selection when communication error is detected.
F17.08 defines the selection of protection action when external communication fault occurs in
communication command setting mode.
0: Freewheel stop.
1: Emergency stop.
2: Dec. stop.
3: Continue to run.
F17.09 Communication write function parameter saving EEPROM choice 00 - 11 [01]
Unit: Except of F00.13, F19.03 function parameter, communication EEPROM storage options
Ten: F00.13, F19.03 function parameter communication EEPROM storage options
0: Not save.
1: Save.
Note:
1. When 10 is set to 1, it may damage the inverter. Please exercise caution!
2. Only when using the communication function parameters, the function code is 0x06 or 0x10 is valid.
F17.10 Network communication timeout detection time 0.0 - 600.0 [0.0s]
When the interval between two receptions of correct data (including local or non-native) continues to exceed
F17.10, the communication timeout is considered to be detected.
• The drive continues to run after a timeout has expired and an E0028 fault (SCI communication timeout) has
been reported.
• F17.10 = 0, do not detecte fault time.