7.14 F16: Analogue Input / Output Terminal Parameter
Ref. Code Function Description Setting Range [Default]
F16.00 Keypad potentiometer function 0 - 12 [0]
F16.01
AI function
0 - 12 [2]
0: Resevered.
2: Frequency setting.
F00.10 = 3 (the channel is set by the analog input setting frequency), the setting frequency will be set by
the corresponding input voltage value of the analog channel whose function is selected.
3: Auxiliary frequency setting.
F19.00 = 4 (setting by the analog auxiliary frequency setting, the auxiliary frequency setting will be set by
the corresponding input voltage value of the analog channel whose function is selected.
4: Process PID setting.
When F04.01 = 1 (setting by the analog setting process PID), the process PID setting will be set by the
corresponding input voltage value with the analog channel that selects this function.
5: PID feedback process.
F04.02 = 0 (feedback from analog input process PID), the process PID feedback will be set by the
corresponding input voltage value of the analog channel whose function is selected.
9: Motor FWD rotation torque limit.
F10.09 tens = 1 (the motor limits the motor FWD rotation by analog input), the motor FWD torque limit is
set by the corresponding input voltage value of the analog channel whose function is selected.
10: Motor reversing motor torque limit.
F10.09 tens = 1 (the motor reverses the motor torque limit channel by analog setting), the motor REV
motor torque limit is set by the corresponding input voltage value of the analog channel whose function
is selected.
11: Motor FWD regenerative torque limit.
F10.10 bits = 1 (the channel is set by analog setting FWD rotation regenerative torque), the limit of motor
FWD rotation regenerative torque is set by the corresponding input voltage value of the analog channel
whose function is selected.
12: Motor REV regenerative torque limit.
F10.10 tens = 1 (defined by the analog setting motor REV regenerative torque limit channel), the motor
REV regenerative torque limit is set by the input voltage value corresponding to the analog channel
whose function is selected.
F16.05
AI offset
-100.0 - 100.0 [0.1%]
F16.06 AI gain -10.00 - 10.00 [0.01]