Shenzhen Hpmont Technology Co., Ltd. Chapter 8 Troubleshooting and Maintenance
HD09-S Series User Manual V1.1 - 75 -
Fault Fault reasons Counter-measures
E0021
Access fault of
control board
EEPROM
Memory circuit fault of control
board EEPROM
Please contact the supplier for
repairing
E0022
Operation keypad
EEPROM read and
write problems
The control keypad EEPROM
memory circuit has failed
Replace the operator keypad
Contact factory maintenance
E0023
Parameter setting
error
The motor rated power is far from
the drive's rated power
Improper motor parameter setting
Select a motor that matches the drive
power
Set the correct motor parameters
(F08.00 - F08.04)
E0024
External equipment
failure
Fault terminal of external
equipment operates
Please check external equipment
E0028
SCI communication
time-out
Connection fault of communication
cable
Disconnected or not well
connected
Please check the connection
E0029
SCI communication
error
Connection fault of communication
cable
Disconnected or not well
connected
Communication setting error
Communication data error
Please check the connection
Please check the connection
Please correctly set the
communication format (F17.00), and
the baud rate (F17.01)
Note:
E0022 does not affect the inverter's normal operation.